What Size UPS Do I Need for an NVR and Security Cameras? (2026)
What size UPS do I need for an NVR and security cameras?
Updated November 2026 · Prices update live from silarius.com
A 4-camera recorder system draws about 40 W and an 8-camera system about 55 W, so a 1500VA / 900W UPS such as the Tripp Lite SMART1500LCDT keeps it recording for about 2 hours 45 minutes at 40 W and almost 2 hours at 60 W. For a shorter outage a 1000VA unit like the CyberPower CP1000PFCLCD is enough; a rack recorder belongs on a rackmount UPS.
Step 1: add up the watts
Count everything that must stay on: the recorder, its hard drives, the cameras it powers over PoE, and the modem and router if you want to watch remotely during the outage.
| Part | Power used | Where the number comes from |
|---|---|---|
| Silarius X 5MP camera (SIL-XD5MP28AU, SIL-XB5MP28AU) | Up to about 4.4 W each on PoE | Product page, max with IR on |
| Silarius X 8MP camera (SIL-XT8MP28AU) | Up to about 5.7 W each on PoE | Product page, max with IR on |
| SIL-NVR4K16 recorder | Up to 10 W without drive or PoE | Product page |
| Each hard drive | Allow 10 W | Safe allowance; check the drive's datasheet |
| Modem and router | Allow 10 W | Safe allowance; check the label |
| System | Add-up | Total |
|---|---|---|
| 4 × 5MP cameras + 16-ch NVR + 1 drive | 17.6 + 10 + 10 W | about 40 W |
| 8 × 5MP cameras + 16-ch NVR + 1 drive | 35.2 + 10 + 10 W | about 55 W |
| 8 × 8MP cameras + 16-ch NVR + 1 drive + router | 45.6 + 10 + 10 + 10 W | about 75 W |
Step 2: pick the runtime you need
Runtime falls fast as the load goes up. Tripp Lite's published chart for the SMART1500LCDT (1500VA / 900W) [1]:
| Load | 40 W | 60 W | 80 W | 100 W | 200 W | 450 W (half) |
|---|---|---|---|---|---|---|
| Runtime | 164 min | 114 min | 85 min | 67 min | 31 min | 10 min [2] |
Estimates from the manufacturer with a new battery; runtime drops as the battery ages.
A 1000VA / 600W UPS such as the CyberPower CP1000PFCLCD is rated for 9 minutes at half load (300 W) [3]; at the 40–60 W of a small camera system it runs much longer, so it covers most short outages for less money.
Step 3: choose the UPS
| UPS | Size | Best for | Price |
|---|---|---|---|
| CyberPower CP850PFCLCD | 850VA / 510W, tower | 4 cameras, short outages | $210.99 |
| CyberPower CP1000PFCLCD | 1000VA / 600W, sine wave, tower | Up to 8 cameras, most offices | $399.99 |
| Tripp Lite SMART1500LCDT | 1500VA / 900W, tower, 10 outlets | 8–16 cameras, longest runtime here | $491.99 |
| CyberPower OR1500LCDRM1U | 1500VA / 900W, 1U rackmount | Rack NVRs such as the SIL-NVR16CHPOE | $782.99 |
| APC SMC1500C | 1500VA, tower, SmartConnect | APC sites, remote battery alerts | $810.99 |
| APC SMT1500RM2UC | 1500VA, 2U rackmount, SmartConnect | APC rack sites | $1,301.99 |
Size and form factor are from each product title.
Keep recording even if the power stays off
A UPS buys minutes or hours. To keep footage safe past that, or if the recorder is stolen, record Silarius X cameras straight to Silarius Cloud from $6.99 per camera per month, or connect your existing NVR or DVR through the Silarius Gateway. Put the modem and router on the UPS so the upload keeps going.
Sources
- Tripp Lite SMART1500LCDT estimated runtime chart (20–900 W), checked November 2026. assets.tripplite.com/ups-runtime-chart/smart1500lcdt-runtime-chart-en.pdf
- Eaton product page SMART1500LCDT, runtime at half and full load, checked November 2026. www.eaton.com/us/en-us/skuPage.SMART1500LCDT.html
- CyberPower CP1000PFCLCD datasheet, runtime at half and full load, checked November 2026. store.cablesplususa.com/content/CyberPower-datasheet-CP1000PFCLCD.pdf
Related guides
- How much NVR storage do I need?
- The best NVR for your cameras
- What size PoE switch do I need?
- How many cameras a small office needs
- All buying guides
Questions
What size UPS do I need for an NVR?
Add up the recorder, drives and PoE cameras: a 4-camera system is about 40 W and an 8-camera system about 55 W. A 1000VA unit covers short outages; a 1500VA / 900W unit such as the Tripp Lite SMART1500LCDT runs 40 W for about 164 minutes and 60 W for about 114 minutes on its manufacturer chart.
How long will a UPS run my security cameras?
It depends on the load. On the Tripp Lite runtime chart, a 1500VA / 900W SMART1500LCDT runs 40 W for 164 minutes, 60 W for 114 minutes and 100 W for 67 minutes.
How much power do security cameras use?
Silarius X 5MP cameras draw up to about 4.4 W each on PoE and 8MP models up to about 5.7 W, with night IR on.
Should the router be on the UPS too?
Yes, if you want to watch remotely or keep recording to the cloud during the outage. Allow about 10 W for a modem and router.
Do I need a rackmount UPS?
Only if the recorder sits in a rack. The CyberPower OR1500LCDRM1U is 1U; the APC SMT1500RM2UC is 2U.
What if the power is out longer than the battery lasts?
Record to Silarius Cloud: Silarius X cameras upload straight to it, and existing NVRs and DVRs connect through the Silarius Gateway.