The inputs on the SK-ZONE-6 share a common FACP signaling line circuit (SLC) input, and the initiating device circuits share a common external power supply. Otherwise, each input on the module operates independently from the others. If needed, you can disable a maximum of two unused inputs on the SK-ZONE-6 board.
It transmits the status of a zone of two-wire detectors to the FACP. Status conditions are reported as normal, open, or alarm. The SK-ZONE-6 supervises the zone of detectors and the connection of the external power supply. All two-wire detectors being monitored must be UL compatible with the SK-ZONE-6
Main Features
- Converts a conventional two-wire loop to an SLC loop
- Six zone inputs
- Fully supervised
- Support for Class B and Class A wiring
- Removable 12 to 18 AWG plug-in terminal blocks
- Individual LED for each relay contact
- Two module mounting in the IDP-ACB cabinet
- Up to two unused modules can be disabled
- Rotary address switches for fast installation
- Mounting hardware included
- UL Listed